Copper compression lugs – Two hole narrow with inspection window

Material

  • E-Copper

Finish

  • 1 Electrotinned: ending with ‘P’, uncoated: ending with ‘U’

Features

  • Available without inspection window part number starting with ‘ SCLH ‘
  • Available in 45º and 90º barrel orientations
  • Available with champher or flare entry

Notes

  • U.L. listed for 35kV max when properly installed
  • Color coded for appropriate crimping (see crimping guideline)
  • Narrow pad tongue width for limited space application
  • RoHS compliant
Catalogue no. Cable size ФE ID W G L Strip Length Color Code Burndy Die Index T&B Die Index
AWG mm²
SCLG-N-2-1/4AP 2 AWG 35 1/4 0.33 0.43 0.63 2.53 0.86 BROWN 10 33
SCLG-N-2-1/4BP 1/4 0.43 0.75 2.61 0.86
SCLG-N-2-1/4CP 1/4 0.43 1.00 2.93 0.86
SCLG-N-1-1/4BP 1 AWG 50 1/4 0.35 0.45 0.75 2.63 0.89 GREEN 11 37
SCLG-N-1/0-1/4CP 1/0 AWG 1/4 0.39 0.51 1.00 2.96 0.89 PINK 12 42
SCLG-N-1/0-5/1CP 5/16 0.51 1.00 3.12 0.89
SCLG-N-2/0-1/4AP 2/0 AWG 70 1/4 0.45 0.56 0.63 2.78 0.93 BLACK 13 45
SCLG-N-2/0-1/4CP 1/4 0.56 1.00 3.10 0.93
SCLG-N-2/0-5/1AP 5/16 0.56 0.63 2.94 0.93
SCLG-N-2/0-5/1CP 5/16 0.56 1.00 3.26 0.93
SCLG-N-350-3/8CP 350 Kcmil 185 3/8 0.71 0.87 1.00 3.52 1.16 RED 18 71
SCLG-N-500-3/8CP 500 Kcmil 240 3/8 0.85 1.06 1.00 3.63 1.26 BROWN 20 87
SCLG-N-500-1/2CP 1/2 1.06 1.00 3.95 1.26
SCLG-N-750-3/8CP 750 Kcmil 3/8 1.04 1.29 1.00 4.24 1.46 BLACK 24 106
SCLG-N-750-1/2CP 1/2 1.29 1.00 4.24 1.46